DIAGNOSTICS

The CAB Skyline slush machine is one of the most reliable slush machines on the market.
A basic design with no troublesome electronics that other machines suffer from.
These slush machines are so easy to repair and maintain we are the only company that will help you fix it yourself.
In the following pages we have listed some of the most common problems with instructions on how to make repairs and parts that may be required.

FAULT

Dispensing tap Dripping

CAUSE

Seals worn or damaged
Tap worn or damaged
Bowl damaged

SOLUTION

Clean the machine weekly and replace the seals annually

FAULT

Syrup leaking from rear of bowl
Drip tray filling from overflow pipe

CAUSE

Seal worn or damaged
Bowl damaged

SOLUTION

Clean the machine weekly and replace the seals annually

FAULT

Syrup leaking and appearing under the machine

CAUSE

Spiral back seal worn or damaged
Bowl inner bush missing

SOLUTION

Replace or reseal

FAULT

Spiral not turning

CAUSE

Gearbox / motor damaged
Brass connecting sleeve split
Electrical fault.
Spiral end damaged

SOLUTION

Replace or reseal

FAULT

One bowl not freezing or over freezing
Other bowls working fine

CAUSE

Consistency regulator not setup correctly
Week spring on consistency regulator
Solenoid coil faulty
Solenoid valve faulty
Micro switch faulty
Weak or damaged gearbox motor assembly
Incorrect water to syrup ratio

FAULT

Machine takes a long time to freeze or does not freeze at all

CAUSE

Condensor dirty or blocked
Fan not working
Low on gas
Compressor is faulty

SOLUTION

  1. First make sure the correct solution is in the machine, the incorrect syrup to water ratio will change the freezing characteristics of the product.
    A slush machine will not freeze water!
  2. Fan motor not working or insufficient air flow.Its possible you can hear the fan running but this may not be the case, If the fan is not spinning correctly the freezing time will either increase or it may not freeze at all.
    Remove the back panels to check.
    A quick cheat is to place a piece of paper on the left hand “Side” panel. If the fan is working correctly the paper will stick.Check air flow arrond the machine, there must be at least 50mm gap all around the machine. More is preferable.
  3. Dirty or blocked condensor.
    (This is the biggest cause of freezing malfunction)The cooling fan sucks air through the condenser and with it lots of dirt, dust and grease resulting in an airflow issue.
    The condenser should be cleaned regularly as part of your cleaning schedule.
    However, they can still get blocked and need a more detailed clean.
    Using compressed air blow the dust out of the condenser removing as much dirt as you can.
    This is usually enough to clear it.
    If it is particularly greasy a service engineer will need to carry out a deep clean.
  4. Refrigeration system low on gas or the compressor is faulty.
    This means there is a leak that must be fixed. Call a commercial refrigeration engineer.